Appendix A Runtime Templates
REMOTE LOWER BRKPT Field
This field specifies the lower breakpoint, BP1, for the remote variable adaptive
function. The gain or reset changes when the remote variable becomes less than the
lower breakpoint.
Valid entry is decimal value with same type of units as the remote variable
(engineering units or percent).
REMOTE UPPER FACTOR Field
This field specifies the multiplier of the base gain or reset associated with the upper
breakpoint, BP2, of the remote variable adaptive function. Valid entry is a decimal
value.
REMOTE LOWER FACTOR Field
This field specifies the multiplier of the base gain or reset associated with the lower
breakpoint, BP1, of the remote variable adaptive function. Valid entry is a decimal
value.
OUTPUT UPPER BRKPT Field
This field specifies the upper breakpoint, BP2, for the output adaptive function. The
gain or reset starts to change when the size of the output becomes greater than the
upper breakpoint. Valid entry is a decimal value in percent.
OUTPUT LOWER BRKPT Field
This field specifies the lower breakpoint, BP1, for the output adaptive function. The
gain or reset starts to change when the size of the output becomes less than the lower
breakpoint. Valid entry is a decimal value in percent.
OUTPUT UPPER FACTOR Field
This field specifies the multiplier of the base gain or reset associated with the upper
breakpoint, BP2, of the output adaptive function. Valid entry is a decimal value.
3BUR002418-600 A
Adaptive Gain
247