PID Controller FCM
BAD OUTPUT ALARMS Field
This field specifies whether the bad data quality alarm for the output signal is
enabled. If this field is YES, an alarm occurs when the data quality of the output
goes to BAD. Valid entries are: YES (enable the alarm), NO (disable the alarm).
SETPOINT HIGH ALARMS Field
This field specifies whether the high alarm for the setpoint signal is enabled. If this
field is YES, an alarm occurs when the output is equal to or greater than the value
entered in the SETPOINT HIGH LIMIT field. Valid entries are: YES (enable the
alarm), NO (disable the alarm).
SETPOINT LOW ALARMS Field
This field specifies whether the low alarm for the setpoint signal is enabled. If this
field is YES, an alarm occurs when the setpoint is equal to or less than the value
entered in the SETPOINT LOW LIMIT field. Valid entries are: YES (enable the
alarm), NO (disable the alarm).
BAD SETPOINT ALARMS Field
This field specifies whether the bad data quality alarm for the setpoint signal is
enabled. If this field is YES, an alarm occurs when the data quality of the setpoint
goes to BAD. Valid entries are: YES (enable the alarm), NO (disable the alarm).
DEVIATION HI ALARMS Field
This field specifies whether the high alarm for the deviation signal is enabled. If this
field is YES, an alarm occurs when the deviation is equal to or greater than the value
entered in the DEVIATION HIGH LIMIT field. Valid entries are: YES (enable the
alarm), NO (disable the alarm).
DEVIATION LOW ALARMS Field
This field specifies whether the low alarm for the deviation signal is enabled. If this
field is YES, an alarm occurs when the deviation is equal to or greater than the value
entered on the DEVIATION LOW LIMIT field. Valid entries are: YES (enable the
alarm), NO (disable the alarm).