Appendix A Runtime Templates

Output FCMs

This section describes the active runtime fields on the output FCM templets.

Common Fields

INITIAL OUTPUT MODE Field or INITIAL MODE Field
These fields indicate the output mode for the loop at start-up and the TRIO
warmstart action. Valid entries are:
INITIAL OUTPUT Field
This field determines the initial result (output of the FCM) at start-up of the FCM.
Valid entry is a decimal number.
BAD INPUTS ACCEPTED? Field
This field specifies the data qualities acceptable for the input signal to the FCM and
the action to take if the data quality becomes unacceptable. Valid entries are:
ACTION ON ERROR Field
This field defines the action taken if the FCM is unable to output a valid signal to the
field. Valid entries are:
3BUR002418-600 A
AUTO
loop determines output values
MAN
operator determines output values
YES
GOOD and BAD are acceptable data qualities
NO
GOOD is the only acceptable data quality for the input
NOTHING
continue processing the loop as configured
FCM OFF
turn the FCM off
SOURCE OFF
turn the source off
GOTO BACKUP for switchover to Backup Controller in Controller
Subsystems with Backup Controller option. For other
Output FCMs
253