Appendix A Runtime Templates
The default value is 0 (zero).
Examples from above:
All with No Supervision
hex number = 205A0000
converted to decimal = 542769152
All with Supervision
hex number = 205A00FF
converted to decimal = 542769407
Channels 4 through 1 with Supervision
hex number = 205A000F
converted to decimal = 542769167
Channels 8 through 5 with Supervision
hex number = 205A00F0
converted to decimal = 542769392
Channels 7, 2 and 1 with Supervision
hex number = 205A0043
converted to decimal = 542769219
VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to S800 I/O
User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.