Appendix A Runtime Templates
The default value is 128.
LABEL
Enter a characteristic name to identify the AO820 Module of the station. The name
may contain up to 20 characters.
OSP HOLD 01 through 04
If an OSP TIMEOUT has occurred, will the AO810 hold the last value during OSP?
Enter a YES if it will, or enter a NO if an OSP VALUE will be used.
The Default is NO.
OSP TIMEOUT
Enter the time (msec) after communications is lost, that outputs go to OSP value.
The valid values are:
OFF, 256, 512, and 1024.
The default value is 1024.
OSP VALUE 01 through 04
Enter the channel value in counts to output after an OSP TIMEOUT. If the OSP
HOLD has been selected as the OSP value then this field entry is ignored.
The default is 0.
The valid values are:
0 to 28480.
Where 0 = 0 mA and 28480 = 20 mA.
Output
Range
-10 - 10V
-20 - 20MA
3BUR002418-600 A
Minimum
Maximum
Count
Count
-28480
28480
-28480
28480
Counts
2848 V/count
1424 mA/count
AO820
299