Analog Output FCM

Analog Output FCM
SIGNAL INVERSION Field
This field indicates whether the output signal is inverted before it is sent to the I/O
Module. For details see INPUT SOURCE field in Section 8.2, Parameters Common
To All Output FCMS.
Valid entries are:
ENGU OR PERCENT Field
This field specifies whether the FCM input is converted from engineering units or
percent. This determines which scaling equation is used to change input to counts.
Valid entries are:
COUNTS - LOWER BOUND Field
This field specifies the raw counts lower limit corresponding to the engineering
units lower bound. Valid entry is an integer between 0 and 32767.
COUNTS - UPPER BOUND Field
This field specifies the raw counts upper limit corresponding to the engineering
units upper bound. Valid entry is an integer between 0 and 32767.
254
Controller and Multibus I/O Subsystems, this choice shuts
down CCF processing when an error condition occurs.
LOOP OFF
turn the loop off
YES
invert the signal
NO
do not invert the signal
ENGU
convert input from engineering units
PERCENT convert input from percent