Section 7 I/O Displays
The top of the S800 Station display identifies the I/O Station, its Advant Controller
and has other information as described below.
Devsub
State
Name
Lan
Station
Templet
Label
RPT Faults
Media
3BUR002418-600 A
The controller DCN address where the S800 I/O is located.
This field shows the status of the controller as ACTIVE, DOWN or
AVAIL.
The controller subsystem part of the logical name created during
database configuration.
This field represents the number of the Local Area Network (LAN)
for all the stations shown. For the AC 460 this is LAN # 1 - 4 and
for the AC 410 this is LAN # 1 or 2.
Go back to the controller display to select a different LAN.
This field represents the number of the station.
Go back to the LAN display to select a different station.
The logical device name created during database configuration is
given in this field.
Descriptive label associated with templet.
Indicates the reporting method for fault condition. FLASH NOTIFY,
SILENT NOTIFY or NO NOTIFY.
This shows the status of the AF 100 bus media.
NONE means that no bus is connected.
BOTH means that dual media is used and that both are
operational.
CABLE 1 UP or CABLE 2 UP shows if only one bus is
connected and operational.
S800 Station Display