Bus Out For The Bcl 500 I; Table 7.5; Pin Assignment Bus Out - Leuze electronic BCL500i Technical Description

Hide thumbs Also See for BCL500i:
Table of Contents

Advertisement

7.2.5
BUS OUT for the BCL 500
To set up the Leuze multiNet plus network with additional participants, the BCL 500
available another interface in the form of an RS 485.
BUS OUT RS 485
VCC485 1
RS485A
M12 socket
(B-coded)

Table 7.5:

Notice!
Ensure adequate shielding. The entire connection cable must be shielded and earthed. The
signal lines must be stranded in pairs.
Termination of the RS 485 interface at the master
The RS 485 interface must always be externally terminated at the master with the use of a
T-connector and a terminating resistor (see chapter 13 "Type overview and accessories").
Termination of the RS 485 interface on the slave
On the last network device, the Leuze multiNet plus network (RS 485 interface) should be
terminated with a terminating resistor (see chapter 13 "Type overview and accessories") on
the BUS OUT socket.
Attention!
The BCL
500i
socket and via an external M12 T-connector! For further information, see chapter 7.4.3 and
figure 7.9!
Leuze electronic
BUS OUT RS 485 (5-pin socket, B-coded)
RS485B
2
GND485
3
5
4
FE
Thread

Pin assignment BUS OUT

can only participate as a slave in the Leuze multiNet plus on the BUS OUT
BCL 500
i
Pin
Name
1
VCC485
2
RS 485 B RS 485 B - signal line
3
GND 485
4
RS 485 A RS 485 A - signal line
5
FE
FE
i
i
\ BCL 501
Electrical connection
Remark
+5VDC for bus termination (termina-
tion)
Reference ground RS 485 - potential
equalisation
Functional earth / shield
Functional earth (housing)
i
makes
79

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bcl501i

Table of Contents