Ethernet cable assignment
2
1
1
Figure 7.10: HOST / BUS IN cable assignments on RJ-45
NOTICE
Ensure adequate shielding. The entire interconnection cable must be shielded and earthed. The RD+/
RD- and TD+/TD- wires must be stranded in pairs. Use CAT 5 cable for the connection.
7.6

BUS OUT

To set up an Ethernet network with other participants with linear topology, the device makes available
another Ethernet interface. The use of this interface drastically reduces the cabling requirements, as only
the first BCL 608i requires a direct connection to the switch, via which it can communicate with the host.
All other BCL 608i are connected in series to the first BCL 608i (see figure 7.13).
2
3
1
4
Figure 7.11: M12 socket (D-coded)
Table 7.5:
Pin
Name
1
TD+
2
RD+
3
TD-
4
RD-
Thread
FE
 For the connection of two devices, the "KB ET - ... - SSA" ready-made cables are preferred (see
table 16.3).
If using self-made cables, observe the following notice:
NOTICE
Ensure adequate shielding. The entire interconnection cable must be shielded and earthed. The signal
lines must be stranded in pairs. Use CAT 5 cable for the connection.
For the device as standalone device or as the last participant in a linear topology, termination on
the BUS OUT socket is not mandatory!
7.7

Ethernet topologies

Various product variants of the BCL 600i series are available for connecting to different fieldbus systems
such as PROFIBUS DP, PROFINET-IO and Ethernet.
Leuze electronic
3
4
Twisted pair
Pin assignment BUS OUT
Comment
Transmit Data +
Receive Data +
Transmit Data -
Receive Data -
Functional earth (housing)
1
8
BCL 608i
Electrical connection
33