Bus Out For The Bcl 504 I; Profibus Termination; Line Lengths And Shielding; Table 7.5 - Leuze electronic BCL500i series Technical Description

Hide thumbs Also See for BCL500i series:
Table of Contents

Advertisement

7.2.5
BUS OUT for the BCL 504
To set up the PROFIBUS with additional participants, the BCL 504
interface of type DP OUT - outgoing PROFIBUS DP.
BUS OUT
A (N)
VP 1
B (P)
M12 socket
(B-coded)

Table 7.5:

Notice!
Ensure adequate shielding. The entire connection cable must be shielded and earthed. For
connecting DP IN and DP OUT, we recommend the ready-made PROFIBUS cables. See
"Accessory ready-made cables for bus connection" on page 189.
7.2.6

PROFIBUS termination

The last physical PROFIBUS participant must be terminated with a terminating resistor (see
"Accessory terminating resistor" on page 187) on the BUS OUT socket.
7.3

Line lengths and shielding

Observe the following maximum line lengths and shielding types:
Connection
BCL – service
PROFIBUS
BCL – power
supply unit
Switching input
Switching output
Table 7.6:
Leuze electronic
i
BUS OUT RS 485 (5-pin socket, B-coded)
2
GND485
3
5
4
FE
Thread

Pin assignment BUS OUT

Interface
USB
PROFIBUS DP

Line lengths and shielding

Pin
Name
1
VP
2
A (N)
3
GND 485
4
B (P)
5
FE
FE
Max. line length
3m
Acc. to PNO speci-
fications
30m
10m
10m
BCL 504
i
Electrical connection
i
makes available another
Remark
+5VDC for bus termination (termina-
tion)
Receive/transmit data A-line (N)
RS 485 ground reference for bus ter-
mination
Receive/transmit data B-line (P)
Functional earth / shield
Functional earth (housing)
Shielding
Shielding absolutely necessary
acc. to USB specifications
Acc. to PNO specifications
not necessary
not necessary
not necessary