Measurements; Standard Measure - ABB SACE Tmax XT2 User Manual

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Measurements

26 - Standard Measure

Standard measurements are:
List
Name
Real-time currents
Events
Openings
Min-Max
measurements
Maintenance
Counter operations
Real-time
The real-time currents, available on the Main page and the Summary pages, are the real-time
currents
measurements of phase and ground fault currents expressed in effective value. The
measurement range and the performance depend on the rated current defined by the rated size
of the Trip unit:
Measurement
Phase currents
Ground fault
Special representations
Type of
measurement
Phase currents
ground fault currents
1SDH002031A1002
ECN000092998
Description
Real-time measurements of phase currents
List of events, status changes, alarms, recorded by the Trip
unit
List of trips (TRIP) for current protections
Log of minimum and maximum currents, recorded with
adjustable interval
CB status: contact wear and last maintenance
Number of mechanical and electrical operations
Measurement range
(min-max)
0.03 .. 64 In
0.08 .. 64 In
(2)
(1)
(2)
Available with LSIG versions
(3)
package is present, and for all other trip unit models, check the performance
shown on page 103
Measurement <
min value
. . . .
Rev. B
Normal operating
range
0.2 .. 1.2 In
0.2 .. 1.2 In
Measurement >
Display: "_ _ _" (not
max value
available) for
> [64 In]
Sensors disconnected
SACE Tmax XT2 - XT4 | 96
Page
96
97
97
98
99
99
Accuracy of
(1)
detected value
(3)
1%
(3)
2%

Hide quick links: