ABB SACE Tmax XT2 User Manual page 143

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Remote
From the service connector (via Ekip Connect) or with communication by system bus it is possible
configurations
to access additional parameters
Parameter
Client/Server
Enable IEEE 1558
IEEE 1588 Master
IEEE 1588 Delay
mechanism
Enable SNTP client
SNTP Server Address
Time zone
Daylight Saving Time
Disable Gratuitos ARP
Access protected by
password
TCP Modbus
password
From the service connector (via Ekip Connect) or with a system bus communication, additional
Remote
information can be accessed:
information
Information
HW and Boot version
Flash CRC status and result
Ekip Link status
SNTP Server Error
SNTP Server Synchronisation
IEEE 1558 status
1SDH002031A1002
ECN000092998
Description
Parameter for changing the configuration of the module from
Server Only to Client and Server and integrating the module into
an interactive data exchange network (see Ekip Com Hub on
page156)
IMPORTANT: if Client/Server, the module enables
the data to be exchanged as a normal Server
function
Permits the IEEE 1588 protocol for distributing the clock and
synchronization signal to be enabled
Enables the module to be set as a master in the network segment
to which it belongs (synchronization clock)
Enables the data exchange mode between module and master,
between Peer-to-Peer and End-to-End to be chosen
Permits enabling of SNTP distribution protocol of the clock and
synchronization signal
Enables the network server to be set that supplies SNTP
Defines the time zone to be used for synchronism
Enables it to be selected whether there is daylight saving
time(ON) or not (OFF) in the country to which the synchronization
time refers.
Permits (Enabled ARP) the periodic generation of a Gratuituos
ARP message to be enabled that is used by Ekip Connect to find
rapidly the modules with Ethernet scanning without its IP address
being known beforehand
Enables the writing operations conducted by the network to be
protected by a password (password request)
With access protected by enabled password, this is the password
to use before each writing session
NOTES:
(1)
Enable IEEE 1558 and Enable SNTP client must not be enabled simultaneously
(2)
the parameter can be modified only by system bus in remote configuration
Rev. B
(1)
(1)
(2)
Description
general module information
information on the correctness of the SW in the module
Signals connection errors of the Ethernet cable
Communication error with the SNTP server
Synchronism status with SNTP server
Valid with IEEE 1588 Master = ON, communicates the presence
(Slave or PTP Master Active) or absence (PTP Master but
Passive) of a higher level master
Default
Server
only
OFF
OFF
End-to-
End
OFF
0.0.0.0
+00:00
OFF
ARP
enabled
Standard
mode
Local
access
SACE Tmax XT2 – XT4 | 143

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace tmax xt4

Table of Contents