The activation of the local bus – essential to start the communication between the module and
Menu
the Trip unit – is available in the Settings menu (page 29).
If the Ekip CI module is correctly detected by Ekip Touch, the corresponding configuration,
measurement, test, and information areas are activated in the respective menus.
Configuration
In the Settings-Modules-Ekip CI menu it is possible to configure the parameters of the module:
Parameter
Enable
Polarity
Delay
If Ekip CI is correctly detected by Ekip Touch, the specific area for the module is made available
Measurements
in the Measurements menu, where the temperature measurement of the PT100 probe is
displayed if connected and active.
Test
If the Ekip CI module is correctly detected, the test area is activated in the Test menu.
For more on the test see page 30.
If Ekip CI is correctly detected by Ekip Touch, the specific area for the module is made available
Information
in the Information-Modules menu, displaying:
Remote
Some additional information regarding the version and status of the module are available from
information
the service connector (via Ekip Connect) or the system bus communication: HW and Boot
version, CRC status (correctness of the SW on the module).
1SDH002031A1002
ECN000092998
Description
Enable/disable some functions and the availability of the
parameters in the menu
 If On: all the inputs and outputs are active, as are their functions
 If Off: only input I61 is active. The O61 control function is off
Defines if input I63 is interpreted as On by Ekip Touch when it is
open (Active open) or when it is closed (Active closed)
Minimum duration of activation of input I63 before sending the
reopening command for contact O61. The delay is expressed in
seconds, which can be set in a range: 0 s .. 100 s with 0.01 s steps
NOTES:
If the input is deactivated before this time has
elapsed, the re-opening command is not sent
With delay = 0 s, the input must still be present for
more than 300
NOTE: if no probe is detected the value "- - -" is displayed
The module's serial number and version
The activation state for the PT100 temperature probe input
Rev. B
S
SACE Tmax XT2 – XT4 | 180
Default
Off
Active
closed
0.1 s