ABB SACE Tmax XT2 User Manual page 135

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Interface
The module has three signalling LEDs:
Figure 33
LED
Power
Rx
Tx
Configurations
Resistances can be linked to bus RS-485, configuring dip switches located on the side of the
module:
Figure 34
Resistances
Rterm
Rpol
1SDH002031A1002
ECN000092998
Description
Reports ON status and correct communication with Ekip
off: module off
fixed or flashing light synchronized on power LED of Ekip
communication with Ekip Touch present
flashing not synchronized with power LED of Ekip
module ON and communication with Trip unit absent
Indicates the status of the communication between the network master and the module (slave):
off: communication between master and module not active
fixed light:communication between master and module active
Indicates the status of the communication between the network master and the module (slave):
off: communication between master and module not active
flashing light: communication between master and module active
Dip switch
1 and 2
3 and 4
IMPORTANT: move the dip-switches before connecting to Ekip Supply module
and to the communication network
Rev. B
Touch
Description
Termination resistance 220 
Move dip switches 1 and 2 to ON position to
connect Rterm
390 pull-up or pull-down resistance 
Move dip switches 3 and 4 to ON position to
connect Rpol
Touch
:
Touch
: module ON and
(two rapid flashes per second):
Default
Off
Off
SACE Tmax XT2 – XT4 | 135