ABB SACE Tmax XT2 User Manual page 189

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Features
Ekip Com EtherNet/IP
Connections
Consult the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
The module is supplied with a 1mt long RJ45 cable to interface with your network.
See the instruction sheets 1SDH002009A1502 to connect the module to Ekip Touch.
Ekip Com EtherNet/IP
Supply
Configurations
Activating the local bus is required to start communication between the module and Ekip Touch
on menu
and is available in the Settings menu (page 114).
If the module is detected correctly by Ekip Touch the following communication parameters can
be configured in the Settings Modules menu:
Parameter
Static IP address
ON
Static IP address
Static Network
Mask
Static Gateway
address
If the module is detected correctly by Ekip Touch in the About-Modules menu the following
Information on
menu
information is available:
Information
SN and version
IP address
Network Mask
Gateway address
MAC Address
1SDH002031A1002
ECN000092998
TM
integrates the following features:
Integrated status contacts (Open / Closed and Trip)
Backup battery to maintain the Date / Time in the event of absence of auxiliary alimetry
NOTA: refer to document 1SDH001000R0509 to replace the backup battery
TM
is supplied directly by the Ekip Touch module to which it is connected .
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Description
Defines whether the module has the dynamic IP
address (Off) or static IP address (On)
If = On all associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
In the presence of several subnets it enables the IP
address to be selected of the node to which the module
is connected
Description
Identification and SW version of the module
Address of the module, assigned to the module by a DHCP server at
the moment of the connection to the network in the event of
configuration with dynamic IP or can be set by menu in the case of a
static IP
Subnet mask; identifies the method for recognizing the subnet to which
the modules belong and enables modules to be searched for within a
defined set of recipients
IP address of the node to which the module is connected, in the
presence of several subnets
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that identifies uniquely the manufacturer of an
Ethernet device
Rev. B
NOTE: without a DHCP server, the module automatically
adopts a causal IP address in the interval 169.254.xxx.xxx
Default
Off
0.0.0.0
0.0.0.0
0.0.0.0
SACE Tmax XT2 – XT4 | 189

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace tmax xt4