OF Protection
Function
If the grid frequency read by the unit exceeds the f13 threshold for a time greater than t13, the
protection sends the TRIP command.
The protection automatically cuts out if the maximum line-to-line voltage value is less than 30 V.
To verify and simulate the trip times based on all the parameters, see:
Parameters
Parameter
Enable
Trip Enable
Threshold
f13
Time t13
Constraints, limitations, and additional functions
From the service connector (with Ekip Connect) or with system bus communication it is also
possible to access the block functions, see page70.
Function
UF2 Protection
The UF2 Protection works like the UF Protection: if the grid frequency read by the unit falls below
the f17 threshold for a time greater than t17, the protection sends the TRIP command.
It is independent of UF protection and it is therefore possible to program thresholds and functions
of the two protections to take advantage of different system solutions (example: signaling with
UF and opening command with UF2 or vice versa, or both for signaling or for tripping).
The protection automatically cuts out if the maximum line-to-line voltage value is less than 30 V.
To verify and simulate the trip times based on all the parameters, see:
Parameters
Parameter
Enable
Trip Enable
Threshold
f17
Time t17
Constraints, limitations, and additional functions
From the service connector (with Ekip Connect) or with system bus communication it is also
possible to access the block functions, see page70.
1SDH002031A1002
ECN000092998
Protection summary table with the operating characteristics (page 79)
Chart with tripping curve (page 90)
Description
Enables/disables protection and availability on menu of the
parameters
Activates/deactivates the open command: if disabled, the alarm
and the lapsing of the protection time are managed only as
information
Defines the value that activates the protection.
The value is expressed both as an absolute value (Hertz) and as a
relative value (Fn), settable in a range:
1 Fn .. 1.1 Fn with 0.001 Fn step
This is the trip time of the protection; the value is expressed in
seconds, which are settable in a range:
0.06 s .. 300 s, with 0.01 s step
Protection summary table with the operating characteristics (page 79)
Chart with tripping curve (page 90)
Description
Enables/disables protection and availability on menu of the
parameters
Activates/deactivates the open command: if disabled, the alarm
and the lapsing of the protection time are managed only as
information
Defines the value that activates the protection.
The value is expressed both as an absolute value (Hertz) and as a
relative value (Fn), settable in a range:
0.9 Fn .. 1 Fn with 0.001 Fn step
This is the trip time of the protection; the value is expressed in
seconds, which are settable in a range:
0.06 s .. 300 s, with 0.01 s step
Rev. B
Default
OFF
OFF
1.1 Fn
3 s
Default
OFF
OFF
0.9 Fn
3 s