Ekip Signalling 2K - ABB SACE Tmax XT2 User Manual

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

49 - Ekip Signalling 2K

Ekip Signalling 2K is an external accessory signalling module that enables programmable
inputs/outputs to be managed.
The module has:
To connect Ekip Signalling 2K to Ekip Touch, the Ekip Cartridge (page 129) and Ekip Supply
(page 130) accessories are required.
Ekip Touch can be configured with three different Signalling 2K modules: Ekip Signalling 2K-1,
Models
Ekip Signalling 2K-2 and Ekip Signalling 2K-3.
The three modules are identical in terms of characteristics and installation methods, except for:
display menus on unit, cablings and addresses for external communication, that are specific for
each model.
All the modules can be connected simultaneously to Ekip Touch to increase the potential of unit
(for example: to increase number of input and output).
Connections
Consult
Supply
Ekip Com Signalling 2K is supplied directly by the Ekip Supply module to which it is connected .
Ekip Touch can be configured in such a way that the status of the inputs corresponds to actions
Input
or signals, with different programming options (see Menu on page 166)
The connection or each input (H11 and H12 for model 2K-1, H21 and H22 for model 2K-2, H31
and H32 for model 2K-3) must be carried out in reference with the common contacts (HC).
The module permits two logic statuses, interpreted by Ekip Touch according to the configuration
selected for each contact:
Status
Open
Closed
1SDH002031A1002
ECN000092998
two contacts for output signals and relative status LED
two digital inputs and relative status LED
a power LED with the startup status of the module
NOTE: if not specified, the information in the following chapter applies to all models
IMPORTANT: in each Ekip Touch can be installed only one module per type; it is
not admitted the connection of two or three equal modules (for example: two Ekip
Signalling 2K-3)
the electrical diagrams for 1SDM000068R0001 for terminal references; for external
cabling, AWG 22-16 cables with a maximum external diameter of 1.4 mm must be used
the instruction sheets 1SDH002009A1503 to connect the module to Ekip Supply and
Ekip Touch.
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Electrical condition
Circuit open
Short circuit
Rev. B
Configuration of contact
Active open
Active closed
Active open
active closed
Status detected by Ekip
Touch
ON
OFF
OFF
ON
SACE Tmax XT2 – XT4 | 165