ABB SACE Tmax XT2 User Manual page 184

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Features
Ekip Com Modbus TCP integrates the following features:
Connections
Consult the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
The module is supplied with a 1mt long RJ45 cable to interface with your network.
See the instruction sheets 1SDH002009A1502 to connect the module to Ekip Touch.
Ekip Com Modbus TCP is supplied directly by the Ekip Touch to which it is connected.
Supply
Modes
Two operating modes are available, which can be configured from the menu:
Modes
TCP
Modbus
Server
HTTP
Activating the local bus is required to start communication between the module and Ekip Touch
Configurations
and is available in the Settings menu (page 114).
on menu
If the module is detected correctly by Ekip Touch in the Modules Settings menu, the following
communication parameters can be configured:
Parameter
Function
Static IP address
ON
Static IP address
Static Network Mask
Static Gateway
address
1SDH002031A1002
ECN000092998
Integrated status contacts (Open / Closed and Trip)
Backup battery to maintain the Date / Time in the event of absence of auxiliary alimetry
NOTA: refer to document 1SDH001000R0509 to replace the backup battery
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Description
Information and commands managed by single requests/questions, according to
mapping and rules of TCP Modbus protocol (see System Interface)
Information and commands available on a web page, which can be accessed by
a browser by inserting the IP Address of the module as the address.
The page has a login window requesting the user password to be entered that is
the same as the password required on the display to modify parameters.
Description
Defines the mode between TCP Modbus and Server
HTTP
Defines whether the module has a dynamic IP (Off)
address or static (On) IP address
If = On all the associated parameters are enabled
Enables static IP to be selected
Enables the subnet mask to be selected
Enables, in the presence of several subnets the IP
address of the node to which the module is connected
to be selected
Rev. B
Default
TCP Modbus
Off
0.0.0.0
0.0.0.0
0.0.0.0
SACE Tmax XT2 – XT4 | 184