ABB SACE Tmax XT2 User Manual page 142

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Modes
Two operating modes are available, which can be configured from the menu:
Modes
TCP
Modbus
Server
HTTP
Configurations
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the Settings menu (page 114).
on menu
If the module is detected correctly by Ekip Touch in the Modules Settings menu, the following
communication parameters can be configured:
Parameter
Function
Static IP address
ON
Static IP address
Static Network Mask
Static Gateway
address
Information on
If the module is detected correctly by Ekip Touch, the following information is available on the
About-Modules menu:
menu
Information
SN and version
IP address
Network Mask
Gateway address
TCP Client 1, 2, 3
MAC Address
1SDH002031A1002
ECN000092998
Description
Information and commands managed by single requests/questions, according to
mapping and rules of TCP Modbus protocol (see System Interface)
Information and commands available on a web page, which can be accessed by
a browser by inserting the IP Address of the module as the address.
The page has a login window requesting the user password to be entered that is
the same as the password required on the display to modify parameters.
Description
Defines the mode between TCP Modbus and Server
HTTP
Defines whether the module has a dynamic IP (Off)
address or static (On) IP address
If = On all the associated parameters are enabled
Enables static IP to be selected
Enables the subnet mask to be selected
Enables, in the presence of several subnets the IP
address of the node to which the module is connected
to be selected
Description
Identification and SW version of the module
Address of the module, assigned to the module by a DHCP server at
the moment of the connection to the network in the event of
configuration with dynamic IP or can be set by menu in the case of a
static IP
NOTE: without a DHCP server, the module automatically
adopts a causal IP address in the interval 169.254.xxx.xxx
Subnet mask; identifies the method for recognizing the subnet to which
the modules belong and enables modules to be searched for within a
defined set of recipients
IP address of the node to which the module is connected, in the
presence of several subnets
IP addresses of the client devices connected to the module (in Server
mode)
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that identifies uniquely the manufacturer of an
Ethernet device
Rev. B
Default
TCP Modbus
Off
0.0.0.0
0.0.0.0
0.0.0.0
SACE Tmax XT2 – XT4 | 142