Configuration
Below is a list of anomalies that can be viewed on the Ekip Touch display and some suggestions
alarms and
for resolving them (in alphabetical order):
suggestions
Signal
Numerical alarm
(e.g. 30002)
Low battery
CB status
CB undefined
Configuration
Configuration session
Contact wear
Ekip Com Hub
Ekip Link Bus
Ekip Signalling 3T
Ethernet disconnected
Internal error
Invalid date
IEEE1588 synch
Local Bus
MAC address
Maintenance
PC Power exceed
Zone Selectivity Diag
Sensor L1/L2/L3/Ne
SNTP error
Switchboard Actor
communication Error
TC disconnected
1SDH002031A1002
ECN000092998
Suggestions
Internal error. For this type of error contact ABB
Replace the battery (see kit sheet 1SDH001000R0509)
Incorrect CB status (example: current present but CB status open)
check the circuit breaker status contacts
Error of configuration of the protection parameters: verify that the I4
threshold and time t4 are compatible with the minimum values for
self-supply
TFTP server enabled and/or configuration session open on the Ekip
Com IEC61850 or Ekip Hub module.
Check the status of the contacts/poles
Problem of the Ekip Com Hub module with: certificates, connected
devices, missing Com modules (RTU or with Ethernet connection),
API TLS device, Hub events, parser configuration
Malfunction of the Ekip Link module: check for loss of connection
with one or more actors
Connection alarm of one or more analog inputs to the Ekip Signaling
3T module
External cable missing on one or more Ekip Com modules equipped
with Ethernet connection
Internal error. For this type of error contact ABB.
Incorrect date and time: set in the menus Settings-System-Date and
Settings-System-Time
Synchronization problem of the IEEE 1588 synchronization module
Unit turned on with auxiliary power supply, Local Bus parameter
enabled but connection to modules not present, incorrect, or
communication lost (for more than five seconds). Check:
connection and startup of the terminal or external modules
that the connected modules are compatible with Ekip Touch
that the Local Bus parameter is: ON (see page 29)
Ekip Com module with wrong/unacceptable MAC address detected
Maintenance alarm: check if the set maintenance interval has been
reached
The average power limit set for the Power Controller has been
exceeded
Error in zone selectivity connections (Selectivity Hardware)
Malfunction in the connection of the sensors to the Trip unit. Check
the status of the power sensors and the correct connection of the
external Neutral sensor
Malfunction with Ekip Com modules: synchronization problem of the
SNTP synchronization module
Verify the configuration and connection of the Ekip Link module
Disconnection of the Trip coil disconnected, verify its operation
Rev. B
SACE Tmax XT2 – XT4 | 18