Logical
The Ekip Link advanced selectivity page includes the parameter Repeat Configuration mask
that allows selecting the protections whose logical selectivity bit – if present at the input – must
Selectivity -
be propagated regardless of the protection state of the current unit.
Repetition
With both hardware and logical selectivity, diagnostics show possible wiring errors of the
Logical
Selectivity -
hardware selectivity signals, verifying their continuity.
Diagnostics
In the Ekip Link Diagnostics Configuration page one can: enable diagnostics, configure the time
interval between one check and the next, select the inputs to check for each active actor
(S/D_Forward, G/D_Backward).
Then:
Logical
Regardless of the diagnostics, if a hardware input is active and none of the logical selectivity bits
of the associated actors are active, a line inconsistency is signaled on the Ekip Link Status page
Selectivity -
for this input.
errors and
inconsistency
A line inconsistency (independent of diagnostics) is indicative of a possible configuration error
(for example: a hardware input of the release and connected to the hardware output of a device
not associated via Link Bus, or of an actor for which the function has not been enabled).
1SDH002031A1002
ECN000092998
NOTE: the parameter acts exclusively on the selectivity bits, it does not affect the
hardware outputs
A check of the hardware inputs is performed at regular intervals
If the input of an actor is configured for diagnostics using Ekip Touch (e.g. input S of actor
3) and the same input is not active at the time of the test, the actor stimulates the output
(e.g. actor 3 activates output S) for a short time: Ekip Touch considers the test outcome to
be positive if it correctly receives the message on its input, otherwise it signals an error
If the hw input is active the diagnostic is not performed: if the input configured for diagnostics
is active at the time of the test, the diagnostic is not performed and the parameter Detection
status in the Ekip Link Status page shows: Unknown
NOTE: to check line inconsistency all the actors associated with the unit are checked,
even those for which the function has not been enabled (the Selectivity Actor parameter
has not been set to the value: True)
To avoid a line inconsistency from being signaled, the devices whose hardware outputs
are connected to the Ekip Touch hardware inputs must also be connected to the Link
Bus and associated with Ekip Touch, while it is not necessary for the function to be
enabled (the Selectivity Actor parameter does not have to be set to the value: True)
Rev. B
SACE Tmax XT2 – XT4 | 77