ABB SACE Tmax XT2 User Manual page 174

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Measurements
Measurement
[2]
Auto detection
Voltage
relation
frequency
relation
Summary Page
The summary page is activated in the presence of the module Ekip Synchrocheck; access is
possible as for the other summary pages (page 24).
In this page, the measures are:
Information
In the About-Modules menu, the specific menu of the module is available, which contains the
serial number and the version of the module
Remote
From the service connector (via Ekip Connect) or with a system bus communication, additional
information
information is available on the version and the status of the module: HW and Boot version, CRC
status (correctness of SW in the module).
1SDH002031A1002
ECN000092998
Description
Busbar active = with automatic detection of the operating mode and operation
with busbar active, or with synchronism function not enabled
Dead busbar = with automatic detection of the operating mode and operation with
dead busbar
--- = Measurement not available (e.g.: because of manual detection of operating
mode)
VintVext = Internal voltage less than or the same as the external voltage
Vin>Vext = Internal voltage greater than the external voltage
--- = Measurement not available (e.g.: because of disabled synchronism or direct
voltage or less than 1 V)
fintfext = Internal frequency less than or the same as the external frequency
fin>fext = internal frequency greater than the external frequency
--- = Measurement not available (e.g.: because of disabled synchronism, or
operation with dead busbar, or frequencies outside measurement range)
NOTES:
(1)
the measurement accuracy of the voltage difference is ± 10 %, unless the
parameter value is 0.02 Un, in which case accuracy is ± 20 %
(2)
the characteristics of voltage and frequency measurements coincide with those
declared on internal inputs (page 96)
V int: voltage read by Ekip Touch
f int: frequency read by Ekip Touch
Δᶲ: phase difference
SYNC: synchronization status
Rev. B
SACE Tmax XT2 – XT4 | 174