ABB SACE Tmax XT2 User Manual page 176

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Input
The module enables the following parameters to be measured
Input
PT1000
4-20mA current loop
Five signalling LEDs are available:
Interface
Figure 45
LED
Power
I 41, I 42,
I 43, I 44
If the Ekip Signalling 3T module is detected correctly, the following areas became available on
Access from
display
the trip unit:
The module configuration is available:
Remote
configurations
In both the conditions, also all the measurements, statuses and alarms of the module are
available.
1SDH002031A1002
ECN000092998
Measurement
Temperature
DC current
NOTES:
(1)
accuracy refers to the 3T module without sensors; for complete accuracy, consider the
characteristics of the sensors and cabling used
(2)
accurate within the range -25 .. 250 °C; in the complete range it is: ± 0.5°C
(3)
the measurement is expressed as a percentage, in which: 0 % = 4 mA and 100 % = 20 mA
(4)
accuracy refers to the full scale: 0.5 %= 0.1 mA
Description
Reports ON status and correct communication with trip unit:
off: module off
fixed or flashing light synchronized with power LED of Ekip Touch: module ON and
communication with Trip unit present
flashing not synchronized with power LED of Ekip Touch (two rapid flashes per
second): module ON and communication with Trip unit absent
Indicate status of the input contacts:
off: input disabled
fixed on: input enabled, sensor connected and measurement valid
flashing: input enabled, sensor not connected and/or measurement not valid
Measurements page, accessible from Home (see page xx), containing the
measurements of all the PT1000 inputs and 4-20mA current loops of both 3T-1 and 3T-
2 modules
information submenu in the Modules-Information menu containing: serial number,
module version and sensors status (Present/Alarm)
IMPORTANT:
if one or more sensors are in alarm status, this signal is activated on
the diagnosis bar: Ekip Signalling 3T
if a sensor is not enables, the reported state is: Present
via Ekip Connect, with communication accessories from service connector or with
communication from system bus
with its own communication system and Ekip Com modules fitted to the circuit-breaker
in the conditions prescribed for the trip unit (use the System Interface for the details)
NOTE: parameters and measurements are distributed on Ekip Connect pages and
communication addresses that are sometimes not consequential; the following tables
show the page references to Ekip Connect 2
Rev. B
Range
Resolution
-50 .. 250 °C
0.01 °C
(3)
0 .. 100 %
0.1 %
SACE Tmax XT2 – XT4 | 176
(1)
Accuracy
± 0.25 °C
(2)
(4)
± 0.5 %