Remote
From the service connector (via Ekip Connect) or with communication by system bus it is possible
configurations
to access additional parameters:
Parameter
Client/Server
Enable IEEE 1558
IEEE 1588 Master
IEEE 1588 Delay
mechanism
Enable SNTP client
SNTP Server Address Enables the network server to be set that supplies SNTP
Time zone
Daylight Saving
Time
Disable Gratuitos
ARP
Access protected by
password
TCP Modbus
password
Further link function parameters are available:
Remote link
configurations
Parameter
Actor link (1-15)
Remote programmable
status (A-D)
Word status (A-D)
Diagnosis
Timeout diagnosis control
Zone selectivity type
Repeat Configuration Mask
1SDH002031A1002
ECN000092998
Description
Parameter for changing the configuration of the module from Server
Only to Client and Server and integrating it into an interactive data
exchange network (see Ekip Com Hubon page156)
IMPORTANT: if Client/Server, the module enables
the data to be exchanged as a normal Server
function
Permits the IEEE 1588 protocol for distributing the clock and
synchronization signal to be enabled
Enables the module to be set as a master in the network segment
to which it belongs (synchronization clock)
Enables the data exchange mode between module and master,
between Peer-to-Peer and End-to-End to be chosen
Permits enabling of SNTP distribution protocol of the clock and
synchronization signal
Defines the time zone to be used for synchronism
Enables it to be selected whether there is daylight saving
time(ON) or not (OFF) in the country to which the synchronization
time refers.
Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
message to be enabled that is used by Ekip Connect to find rapidly
the modules with Ethernet scanning without its IP address being
known beforehand
Enables the writing operations conducted by the network to be
protected by a password (password request)
With access protected by enabled password, this is the password
to use before each writing session
NOTES:
(1)
Enable IEEE 1558 and Enable SNTP client must not be enabled simultaneously
(2)
the parameter can be modified only by system bus in remote configuration
Description
IP address of each actor (1 to15)
Configuration parameters of programmable statuses
Word configuration parameters:
Active (passive diagnosis) or deactivated diagnosis (no
diagnosis) of the diagnosis of cabled selectivity
Diagnosis checking interval, if active available between
30 s, 1 min, 10 min, 60 min
Configuration of hardware selectivity (only HW) or
hardware and logic selectivity (mixed)
interactive mask for selecting selectivity do be sent also
to the upper levels (even if not active on the programmed
device)
Rev. B
(1)
(1)
(2)
actor selection (actor from 1 to 15) that activates
programmable status
event of the actor that determines the change of
programmable status
actor selection (actor from 1 to 15) from which the
word status is taken
selection of the taken word
Default
Server
only
OFF
OFF
End-to-
End
OFF
0.0.0.0
+00:00
OFF
ARP
enabled
Standard
mode
Local
access
Default
0.0.0.0
Actor 1
None
None
1 global
No diagnosis
30 seconds
Only HW
0x0000