Ekip Touch
In the summary pages, with Load Shedding activated the specific page with the main
Measurements
measurements is available:
Measurement
F
Fn
LOADS
LOADS Shed
With Power Controller activated, the Load Shedding menu is available in the Information page
(page 30), and it provides information on the 15 loads in 2 submenus:
Submenu
Load Input Status
Active load
1SDH002031A1002
ECN000092998
Description
Frequency measured
Rated frequency of the Trip unit
Number of controlled loads
Number of loads shed
Information included
Load status (from Load 1 to Load 15): open or closed
Load configuration (from Load 1 to Load 15): active or inactive
Rev. B
SACE Tmax XT2 – XT4 | 123