Additional functions

34 - Power Controller

Description
The Power Controller function allows managing the loads of a system according to the power
absorbed to reduce consumption and optimize energy efficiency.
All the parameters and measurements of the function are available via Ekip Connect, while the
Trip unit allows setting and viewing some of them, as noted below.
Some function configuration parameters are available In the Settings - Power Controller menu
Ekip Touch
Parameters
(page 29).
Parameter
Enable
Load
Operating
Mode
Powers
Limits
Ekip Touch
In the summary pages, with Power Controller activated the specific page with the main
Measurements
measurements is available:
Measurement
Ea
LOADS
LOADS Shed
With Power Controller activated, the Power Controller menu is available in the Information page
(page 30), and it provides information on the 15 loads in 2 submenus:
Submenu
Load Input Status
Active load
1SDH002031A1002
ECN000092998
IMPORTANT: for full details see the Technical Catalog (see page 4) or the
function's White Paper (see page 12).
Description
Enable/disable the function and the availability of the parameters in
the menu
Allows setting the configuration of each of the 15 programmable
loads (from Load 1 to Load 15). It is possible to choose between
Automatic or Manual configuration
Allows setting the 10 power limits (from Power Limit 1 to Power
Limit 10). The value is expressed in kW and can be set in a range
of: 10 kW .. 10000 kW with 10 kW steps.
NOTE: to set all the parameters of the function it is recommended to first configure the
parameters via Ekip Connect, and only then work on the Trip unit to enable or change
loads and power limits
Description
Expected energy
Time spent within the evaluation window
T
Number of controlled loads
Number of loads shed
Information included
Load status (from Load 1 to Load 15): open or closed
Load configuration (from Load 1 to Load 15): active or inactive
Rev. B
Default
OFF
Manual
10 kW
SACE Tmax XT2 – XT4 | 121