ABB SACE Tmax XT2 User Manual page 199

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Remote Link
With regard to the Link functions, additional parameters are available:
configurations
Parameter
Link Actor (1-15)
Remote programmable
status (A-D)
Status Word (A-D)
Diagnosis
Diagnostic timeout check
Zone selectivity type
Repeat Configuration Mask
Remote
From the service connector (via Ekip Connect) or with system bus communication it is also
information
possible to access additional information.
Information
HW and Boot version
Flash CRC status and result
Ekip Link Status
SNTP Server Error
SNTP Server Synchronization
IEEE 1558 status
With regard to the Link functions, additional parameters are available:
Remote Link
information
Information
Line Congruency detection
Remote programmable states
Remote programmable word status
Logical zone selectivity
1SDH002031A1002
ECN000092998
Description
IP address of each actor (from 1 to 15)
Configuration parameters of the programmable states:
Actor selection (actor from 1 to 15) which activates
the programmable status
Event of the actor that determines the change of the
programmable status
Word configuration parameters:
actor selection (actor from 1 to 15) from which the
status word is taken
selection of the word taken
Enable (passive diagnostics) or disable (no diagnostics)
the wired selectivity diagnostics
Diagnostics check interval, if active, select from 30 s, 1
min, 10 min, 60 min
Hardware
selectivity
hardware and logical (Mixed)
Interactive mask for selecting the selectivity to be
forwarded to the higher levels (even if not active on the
programmed device)
Description
General module information
Information on the correctness of the SW on the module
Reports connection errors of the Ethernet cable
Communication error with the SNTP server
Synchronization status with the SNTP server
Valid with Master IEEE 1588 = ON, communicates the presence (Slave
or PTP Master Active) or absence (PTP Master but Passive) of a higher
level master
Description
Information related to the status and inconsistencies of the HW
and logical selectivity (status and type of non-congruent
selectivity)
State (true/false) of the A, B, C and D remote programmable
states
Value of the A, B, C, D remote programmable words
Logical selectivity states (inputs and outputs)
Rev. B
configuration
(HW
only)
SACE Tmax XT2 – XT4 | 199
Default
0.0.0.0
Actor 1
Nobody
Nobody
1 global
No
diagnostics
30 seconds
or
HW only
0x0000

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sace tmax xt4

Table of Contents

Save PDF