ABB SACE Tmax XT2 User Manual page 80

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Motor
Protection
Protections
[ANSI code]
R JAM [51LR]
R STALL [51LR]
UC [37]
U
Protection notes
Performance guaranteed under all operating conditions
Protection
L
S
I / 2I
G
UF / UF2 / OF / OF2
Others
1SDH002031A1002
ECN000092998
Trip time t
t
t
= tj
(7)
t
t
= ts
t
t
= tuc
t
t
= tu
(8)
t
NOTES:
(1)
for the calculation of t
(example: If = 0.8 In, I1= 0.6 In)
(2)
with t4 = instantaneous, the maximum tolerance is 50 ms
(3)
Tolerances valid with the Trip unit in steady state or switched on with auxiliary power
supply, trip time
are not guaranteed, the tolerances in the table following the notes are valid
(4)
The trip unit considers a hysteresis of 3% for exiting the alarm condition
(5)
Tolerance valid for frequencies in the range: fn ± 2%. For frequencies outside the range
there is a tolerance of ± 5%
(6)
± 20% for the 0.4 Hz/s threshold
(7)
Time to be considered valid after the Motor start-up
(8)
Time to be considered valid with protection in an alarm state after the Motor start-up. If
the alarm appears during the Motor start-up, the trip unit calculates and uses the lowest
value between tu and half of Motor start-up
Trip threshold tolerance
Activation in the range: (1.05-1.2) x I1
± 10 %
± 15 %
± 10 %
± 2 %
--
Rev. B
Trip threshold
Trip time tolerance
(3)
tolerance
± 7 % with If  6 In; ± 10 % with If > 6 In
± 10 %
± 10 %
± 10 %
± 15 %
± 20 %
± 15 %
± 20 %
use the values of the trip and threshold currents expressed in In
t
100 ms, temperature and signals within operating limits. If conditions
Trip time tolerance
± 20 %
± 20 %
 60 ms
± 20 % (60 ms with t4 = instant)
± 20 %
± 20 %
SACE Tmax XT2 – XT4 | 80