ABB SACE Tmax XT2 User Manual page 105

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Parameters 2
The submenus Datalogger 1 and Datalogger 2 (available if the selected number of data loggers
is: 2) contain the following options:
Option
Source Stop
Stop Delay
Restart
Stop
Memory Type
With Ekip Connect it is possible to select the Memory Type parameter (Non-volatile/Volatile):
The parameter is set to Non-volatile by default.
If there is a log, Ekip Touch displays the information on the diagnosis bar (DataLog available).
Alerts
Ekip Connect
Ekip Connect 3 has two specific areas for the Datalogger function:
1. Datalogger to configure the log parameters with a simplified graphical interface and to
2. Data Viewer to open and view logs
Both areas are available in Ekip Connect's Tools menu and described in the Help section of the
application.
1SDH002031A1002
ECN000092998
Description
Trigger event that stops the logging. The display shows the main
protection options (openings, timings, alarms) and actuator status
(open/closed).
It is possible to configure the Custom option via Ekip Connect.
Delay in stopping the logging, calculated starting from the
trigger. The value is expressed in seconds, and can be set in a
range: 0 s .. 10 s, with 0.01 s steps.
Log start command (START)
Manual log stop command (STOP)
Non-volatile: Ekip Touch maintains the log even if switched off. The internal battery life of
the unit may decrease considerably with respect to the declared value in cases where there
is a log in the memory and there is no auxiliary power supply.
Volatile: Ekip Touch loses the log if switched off. When the unit is switched back on the data
logger automatically restarts, having lost the previously stored data.
NOTE: Ekip Touch also shows the general indication that a log is available in the
configuration with two dataloggers. Use Ekip Connect to identify which of the two logs
(or both) is available
download the logs
Rev. B
Default
None
0.01 s
SACE Tmax XT2 – XT4 | 105