ABB SACE Tmax XT2 User Manual page 16

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Check
Accessories
accessories [2]
MOE-E energy
storage controller
AUP circuit
breaker status
inputs, for the
removable version
of the CB
1SDH002031A1002
ECN000092998
Checks
1. Check the correct wiring of the MOE-E energy storage controller as per the
wiring diagrams 1SDM000068R0001.
2. Set the circuit breaker to the closed position
3. Supply auxiliary power to Ekip Touch and rated voltage to the MOE-E device
4. Perform an opening test from the Test-CB Test menu with the Open CB
command and make sure that the CB has opened
5. Repeat the test from the Test- CBTest menu with the Close CB command and
make sure that the CB has closed
1. Check that the status of the removable circuit breaker is correctly read by the
Trip unit using the Information-Circuit Breaker-CB Status menu
2. Change the status of the AUP device and verify the Trip unit's correct reading
of the change in status using the Information-Circuit Breaker-CB Status menu
Rev. B
SACE Tmax XT2 – XT4 | 16