46 - Ekip Com IEC 61850

Ekip Com IEC 61850 is a communication accessory that enables Ekip Touch to be integrated
into an Ethernet network with IEC 61850 communication protocol, with remote supervision and
control functions.
The module is configured as master and from remote it is possible to
To map the module in its communication network, the document System Interface is available
(page 128) that lists the necessary communication and command details.
The document also describes configuration files for protocol IEC 61850 and relative loading
procedure for assigning the Technical Name and any GOOSE enabling (by setting relative MAC
Addresses)
Depending on the parameters set, which are illustrated on subsequent pages, the following
module ports are used:
Ethertype
0x0800-IP
0x88B8
0x0800-IP
0x0800-IP
To connect Ekip Com IEC 61850 to Ekip Touch, the Ekip Cartridge (page 129) and Ekip Supply
(page 130) accessories are required.
Safety
As the module enables the actuator to be controlled that is connected to Ekip Touch and enables
unit data to be accessed, it can be connected only to networks meeting all the necessary security
and unauthorized-access prevention requirements (e.g. the control system network of a plant).
1SDH002031A1002
ECN000092998
read information and Ekip Touch measurements
manage certain commands, including opening and closing actuator (MOE-E)
access to information and parameters that are not available on the display
supply vertical communication (reports) to higher supervision systems (SCADA), with
statuses and measurements (retransmitted each time and only if they are different from the
previous report)
supply horizontal communication (GOOSE) to other actuator devices (e.g.: medium voltage
switches), with all information on status and measurements normally shared by Ekip Com
communication modules on bus.
if connected to a withdrawable circuit-breaker, check the status of inserted / extracted
NOTE: the remote open and close commands to the switch can be run only if Ekip
Touch is in Remote configuration
Port
102
-
123 UDP
69 UDP
IMPORTANT:
It is customer's sole responsibility to provide and continuously ensure a
secure connection between the module and customer network or any other
network (as the case may be); customer shall establish and maintain any
appropriate measures (such as but not limited to the installation of firewalls,
application of authentication measures, encryption of data, installation of
anti-virus programs, etc) to protect the product, the network, its system and
the interface against any kind of security breaches, unauthorized access,
interference, intrusion, leakage and/or theft of data or information.
ABB Ltd and its affiliates are not liable for damages and/or losses related to
such security breaches,any unauthorized access, interference, intrusion,
leakage and/or theft of data or information.
The module cannot be connected directly to the Internet; connect only to
dedicated Ethernet networks, with IEC 61850 communication protocol
Rev. B
Protocol
ISO Transport Service on top of the TCP (RFC 1006)
GOOSE Messages
NTP - Network Time Protocol
TFTP - Trivial File Transfer Protocol
SACE Tmax XT2 – XT4 | 151