Input PT100
The I61 analog input (H61 and H62) allows connecting a thermocouple (PT100 model) to monitor
the temperature and, in case of activation of the PTC protection (page 69), to manage a TRIP in
case of alarm (fixed threshold at 120°C)
The contact guarantees the following measurement characteristics:
Input
PT100
The I63 digital input (H63 and H64) allows commanding the reopening of the O61 contact
Input Trip reset
following a TRIP.
The module has two logical states, interpreted differently by the Trip unit according to the polarity
configured by the user:
State
Open
Closed
The re-closing command is activated on the front.
Interface
The module has four signaling LEDs:
Figure 46
LED
Power
I 61
I 63
O 61
1SDH002031A1002
ECN000092998
Measurement
Temperature
NOTES:
(1) Accuracy referred to the Ekip CI module without sensor. For complete accuracy,
consider the characteristics of the sensor and the wiring used
(2) Accuracy valid in the range: -25°C ..- 250°C. In the full range it is: ± 0.5°C
Electrical condition
Circuit open
Short circuit
Description
Signals the status of power on and correct communication with Ekip Touch:
Off: module off
On, fixed or with flashing synchronized with the Ekip Touch Power LED: module
on and in communication with trip unit
Blinking, not synchronized with the Ekip Touch Power LED (2 fast flashes per
second): module on and not in communication with a trip unit
Indicates the status of the PT100 I61 temperature probe:
Off: input disabled
On: input enabled and sensor present
Blinking: input enabled and sensor disconnected or invalid signal
Indicates the status of the digital input for the Trip Reset I63:
Off: input open
On: input closed
Indicates the status of the command contact for the O61 contactor:
Off: contact closed
On: contact open
Rev. B
Range
Resolution
-50 .. 250 °C
0.01 °C
Polarity
Status detected (and command)
Active open
On (O61 open command)
Active closed
Off
Active open
Off
Active closed
On (O61 open command)
(1)
Accuracy
± 0.25 °C
(2)
SACE Tmax XT2 – XT4 | 179