Programmable
Eight commands with programmable activation are available depending on signals or events.
commands
Located in various Ekip Touch menus, the commands are:
Name
External trip
Trip RESET
Switch on SET B
Energy RESET
YO Command
YC Command
Switch On LOCAL
Signalling RESET
Parameters
Each command has two programmable parameters:
Parameter
Function
Delay
1SDH002031A1002
ECN000092998
Description
Sends a TRIP command
Reset of the trip signal
Check protections set, from Set A to Set B
Reset of energy counters
Sends an open command; it's necessary the
presence of MOE-E
Sends a close command; it's necessary the
presence of MOE-E
Configuration change, from Remote to Local
Reset contacts of signalling modules
Description
One or several events (up to eight, in AND or OR logic
configuration) to activate command.
The Custom configuration can be programmed via Ekip Connect
Is the minimum time of persistence of the event before the
command is sent; the value is expressed in seconds, which are
settable in a range: 0 s .. 100 s, with 0.1 s step
IMPORTANT: the commands are sent if all the operating conditions expected by
the units are found (connections, power supplies, alarms, etc.).
Rev. B
Path (page)
Advanced -
Functions (27)
Measurements-
Energy (28)
Settings - Functions
(29)
Settings - Modules
-Functions (29)
Default
Deactivated
0 s