ABB SACE Tmax XT2 User Manual page 163

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Information on
If the module is detected correctly by Ekip Touch in the About-Modules menu the following
menu
information is available:
Information
SN and version
IP address
Network Mask
Gateway address
MAC Address
Remote
From the service connector (via Ekip Connect) or with communication by system bus it is possible
configurations
to access additional parameters:
Parameter
CRL Enable
Clock update
hardening enable
SNTP Server
Location
SNTP Time zone
SNTP Daylight
Saving Time
Disable Gratuitos
ARP
1SDH002031A1002
ECN000092998
Description
Identification and SW version of the module
Address of the module, assigned to the module by a DHCP server at
the moment of connection to the network in the event of configuration
with dynamic or settable IP that can be set by the menu in the event of
a static IP
NOTE: without a DHCP server, the module automatically
adopts a causal IP address in the interval 169.254.xxx.xxx
Subnet mask; identifies the method for recognizing the subnet to which
the modules belong and enables modules to be searched for within a
defined set of recipients
IP address of the node to which the module is connected, in the
presence of several subnets
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that identifies uniquely the manufacturer of an
Ethernet device
Description
Enables the CRL (Certificate Revocation List) to check the
validity of the server certificate
Enables control of the time reference transmitted by the
SNTP server
Enables the position of the SNTP server to be set with
respect to the network in which the module is installed
Defines the time zone to be used for synchronism
Enables it to be selected whether there is daylight saving
time(ON) or not (OFF) in the country to which the
synchronization time refers.
Permits (Enabled ARP) the periodic generation of a
Gratuituos ARP message to be enabled that is used by Ekip
Connect to find rapidly the modules with Ethernet scanning
without its IP address being known beforehand
Rev. B
Default
+00:00
OFF
ARP
enabled
SACE Tmax XT2 – XT4 | 163