ABB SACE Tmax XT2 User Manual page 139

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Menu
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the Settings menu (page 114).
If the module is detected correctly by Ekip Touch two areas are activated:
Parameter
MAC
Address
Baudrate
Remote
From the service connector (via Ekip Connect) or with communication by system bus it is possible
configurations
to access additional parameters:
Parameter
Class ID
Bus-Off
behaviour
Remote
From the service connector (via Ekip Connect) or with a system bus communication, additional
information
information is available on the version and the status of the module: HW and Boot version, CRC
status (correctness of SW in the module).
1SDH002031A1002
ECN000092998
information area in the About-Modules menu containing the software version and the serial
number of the module
area of specific configuration in the Modules Settings menu, in which it is possible to
configure the following communication parameters:
Description
Module address; range from 1 to 63 available
IMPORTANT: devices connected to the same
network must have different directions
Data transmission speeds: 3 options available:
125 kbit/s, 250 kbit/s, 500 kbit/s
NOTE: 63 default of module Ekip Com DeviceNet
TM
DeviceNet
Redundant
Description
Defines the addressing class of the module, between 8
and 16 bit
Defines the behaviour of the module following loss of
communication(Bus-Off), available between Standard (if
the communication is lost, a supply reset is awaited) and
Advanced (the module tries to reset and detects the error
status)
Rev. B
Default
63 /
62
125 kbit/s
TM
; 62 default of module Ekip Com
Default
8-bit Class ID
DeviceNet
standard
SACE Tmax XT2 – XT4 | 139
(NOTE)