Configurations
Activating the local bus is required to start communication between the module and Ekip Touch
on menu
and is available in the Settings menu (page 114).
If the module is detected correctly by Ekip Touch, in the Settings Modules menu, the following
communication parameters can be configured:
Parameter
Static IP address
ON
Static IP address
Static Network
Mask
Static Gateway
address
SNTP client
enabled
SNTP address
Server
Information on
If the module is detected correctly by Ekip Touch in the About-Modules menu the following
menu
information is available:
Information
SN and version
IP address
Network Mask
Gateway
address
MAC Address
Cfg file
Error Cfg file
1SDH002031A1002
ECN000092998
Description
Defines whether the module has the dynamic IP
address (Off) or static IP address (On)
If = On all associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
In the presence of several subnets it enables the IP
address to be selected of the node to which the module
is connected
Permits enabling of SNTP distribution protocol of the
clock and synchronization signal
Enables the network server to be set that supplies
SNTP
Description
Identification and SW version of the module
Address of the module, assigned to the module by a DHCP server at the
moment of the connection to the network in the event of configuration
with dynamic IP or can be set by menu in the case of a static IP
NOTE: without a DHCP server, the module automatically
adopts a causal IP address in the interval 169.254.xxx.xxx
Subnet mask; identifies the method for recognizing the subnet to which
the modules belong and enables modules to be searched for within a
defined set of recipients
IP address of the node to which the module is connected, in the presence
of several subnets
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet
device
Name of the configuration file loaded in the modules
Error code of the configuration file (0 = no error)
Rev. B
Default
Off
0.0.0.0
0.0.0.0
0.0.0.0
OFF
0.0.0.0
SACE Tmax XT2 – XT4 | 153