Safety
As the module enables the actuator to be controlled that is connected to Ekip Touch and enables
unit data to be accessed, it can be connected only to networks meeting all the necessary security
and unauthorized-access prevention requirements (e.g. the control system network of a plant).
Features
Ekip Com IEC 61850 integrates the following features:
Connections
Consult the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
The module is supplied with a 1mt long RJ45 cable to interface with your network.
See the instruction sheets 1SDH002009A1502 to connect the module to Ekip Touch.
Supply
Ekip Com IEC 61850 is supplied directly by the Ekip Touch module to which it is connected .
Configurations
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the Settings menu (page 114).
on menu
If the module is detected correctly by Ekip Touch, in the Settings Modules menu, the following
communication parameters can be configured:
Parameter
Static IP address
ON
Static IP address
Static Network
Mask
Static Gateway
address
SNTP client
enabled
SNTP address
Server
1SDH002031A1002
ECN000092998
IMPORTANT:
It is customer's sole responsibility to provide and continuously ensure a
secure connection between the module and customer network or any other
network (as the case may be); customer shall establish and maintain any
appropriate measures (such as but not limited to the installation of firewalls,
application of authentication measures, encryption of data, installation of
anti-virus programs, etc) to protect the product, the network, its system and
the interface against any kind of security breaches, unauthorized access,
interference, intrusion, leakage and/or theft of data or information.
ABB Ltd and its affiliates are not liable for damages and/or losses related to
such security breaches,any unauthorized access, interference, intrusion,
leakage and/or theft of data or information.
The module cannot be connected directly to the Internet; connect only to
dedicated Ethernet networks, with IEC 61850 communication protocol
Integrated status contacts (Open / Closed and Trip)
Backup battery to maintain the Date / Time in the event of absence of auxiliary alimetry
NOTA: refer to document 1SDH001000R0509 to replace the backup battery
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Description
Defines whether the module has the dynamic IP
address (Off) or static IP address (On)
If = On all associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
In the presence of several subnets it enables the IP
address to be selected of the node to which the module
is connected
Permits enabling of SNTP distribution protocol of the
clock and synchronization signal
Enables the network server to be set that supplies
SNTP
Rev. B
Default
Off
0.0.0.0
0.0.0.0
0.0.0.0
OFF
0.0.0.0
SACE Tmax XT2 – XT4 | 192