Programmable
With the Programmable Logic function it is possible to program the activation of up to four bits of
Logic
the Ekip Link, each bit according to any combination of the status bits of an actor whose IP
address has been entered.
These four bits are referred to as States A B C and D, remotely programmable, and their value
is transmitted to the device to which Ekip Link is connected
Power
With the Power Controller function each actor can:
Controller
The status of the loads can be acquired by checking the status of the inputs of the signaling
modules connected to the actors whose IP Addresses have been included, while the load control
can be performed by programming their outputs.
Remote acquisition of the load states and their control can also be performed with Ekip Signalling
10Ks connected to the network.
More information on the potential of the function is available in White Paper 1SDC007410G0201
"Load management with Ekip Power Controller for SACE Emax 2."
Zone selectivity
With the Zone Selectivity function:
For more information on the Zone Selectivity function with Ekip Link, see page 76.
Supply
Ekip Link is powered directly by the Ekip Touch it is connected to.
The activation of the local bus – essential to start the communication between the module and
Menu
Ekip Touch – is available in the Settings menu (page 29).
configurations
If the module is correctly detected by Ekip Touch, it is possible to configure the following
communication parameters in the Settings-Modules menu:
Parameter
Static IP address ON
Static IP address
Static Network Mask
Static gateway
address
1SDH002031A1002
ECN000092998
Acquire the status and control the loads
Perform the role of master and gather the energy measurements of the actors included as
Energy Meter
Provide energy measurements to actors included as masters
The IP addresses entered refer to the actors with interlocking role compared to the current
one
For each interlocking actor included the protections must be selected for which selectivity
must be implemented by setting a mask. The function thus configured is subsequently
referred to as logical, to distinguish it from the standard that later is also referred to as
hardware
The protections thus selected are added to the S, G, D-Backward and D-Forward hardware
ones
It is possible to choose between only hardware or both hardware and logical selectivity
It is possible to set the diagnostics to check for each interlock release if there is congruence
between the hardware and logical selectivity information
It is possible to set a mask that identifies the protections to which the selectivity information
received will be retransmitted, regardless of whether the actor is in an alarm state. The
mask is applicable only to information about logical selectivity
NOTE: without an auxiliary power supply communication between Ekip Touch and the
module is interrupted
Description
Defines if the module has a dynamic IP address (Off) or static
(On). If = On all the associated parameters are enabled
Enter the static IP address
Enter the subnet mask
With multiple subnets, enter the IP address of the node the
module is connected to
Rev. B
Default
Off
0.0.0.0
0.0.0.0
0.0.0.0
SACE Tmax XT2 – XT4 | 197