52 - Ekip CI

Ekip CI is an accessory module that can be configured with Ekip M Touch that allows the
management of a contactor in Normal configuration (see page 115)
The module has:
To connect Ekip CI to Ekip Touch, the Ekip Cartridge accessories (page 127) and Ekip Supply
accessories (page 130) are required.
Connections
See:
Ekip CI is powered directly by the Ekip Supply module it is connected to.
Supply
Output
The O61 output contact (K61 and K62), normally closed, is opened in case of a TRIP.
Re-closure is possible following a command to the Trip Reset input or, if the Autoreclosure
function is active, after the time defined by the user (Autoreclosure Time).
The contact has the following electrical characteristics:
Characteristics
Rated breaking capacity
Minimum breaking power
Insulation resistance between contact and Trip
unit
1SDH002031A1002
ECN000092998
A contact for controlling a contactor
An input for a PT100 temperature probe (2 wires)
A digital input for the Trip Reset function
LED indicating the module's power on status and the operation of the module
The 1SDM000068R0001 wiring diagrams for connection and terminal references. For
the I61 input use insulated cables for resistance thermometers like PENTRONIC
TEC/SITW-24F (TX type) or similar, with a maximum length of three meters
The kit sheet 1SDH002009A1503 to connect the module to Ekip Supply and Ekip M
Touch
IMPORTANT: the I61 input is not isolated: regardless of the system voltage, the
customer must ensure the insulation between the input and power supply of the
Ekip Supply module according to the application and grid
NOTE: without an auxiliary power supply the communication between Ekip M Touch
and module will be interrupted, the output contact maintains the status, the input signals
are no longer valid.
NOTE: data related to a resistive load
Rev. B
(NOTE)
Maximum limit
8A @ 250 VAC / 5A @ 30 VDC
10 mA @ 5 VDC
1000 MΩ, 50 VDC
SACE Tmax XT2 – XT4 | 178