Features
Ekip Com Profinet integrates the following features:
Connections
Consult the electrical diagrams for 1SDM000068R0001 to connect the module to its
communication network and for terminal references.
The module is supplied with a 1mt long RJ45 cable to interface with your network.
See the instruction sheets 1SDH002009A1502 to connect the module to Ekip Touch.
Ekip Com Profinet is supplied directly by the Ekip Touch module to which it is connected.
Supply
Menu
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the Settings menu (page 114).
If the module is detected correctly by Ekip Touch, the following information is available in the
About-Modules menu:
Information
SN and version
MAC Address
Remote
From the service connector (via Ekip Connect) or with a system bus communication, additional
information
information is available on the version and the status of the module: HW and Boot version, CRC
status (correctness of SW in the module).
1SDH002031A1002
ECN000092998
Integrated status contacts (Open / Closed and Trip)
Backup battery to maintain the Date / Time in the event of absence of auxiliary alimetry
NOTA: refer to document 1SDH001000R0509 to replace the backup battery
NOTE: in the absence of an auxiliary supply, the communication between Ekip Touch
and module is interrupted
Description
Identification and SW version of the module
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that identifies uniquely the manufacturer of an
Ethernet device