ABB SACE Tmax XT2 User Manual page 115

Ekip touch trip units low-voltage molded-case circuit breakers
Hide thumbs Also See for SACE Tmax XT2:
Table of Contents

Advertisement

Bus Test
The parameter allows enabling/disabling the changing of parameters from the service connector,
limiting the possibility of configuring all the options on the display (in Local mode) or from Ekip
Com modules (in Remote mode).
If the parameter is disabled, Local mode and use of the password provide security against
unwanted changes by unauthorized personnel.
Ekip Touch is supplied with the parameter set to: On.
System
The System menu has several options:
Parameter
Data
Time
Language
Password
The View menu allows access to the configuration of the Client Page:
View
Parameter
Client page
Display Contrast
Sets the contrast of the Ekip Touch LCD display.
The parameter allows enabling/disabling an alarm related to unit maintenance, described on
Maintenance
page 99.
Ekip Touch is supplied with the parameter set to: On.
1SDH002031A1002
ECN000092998
NOTE: with Test Bus = Off the communication from the service connector is still
guaranteed (reading is allowed)
Description
Set the current date
Set the current time
Set the language in the display menus
Set the password, see page 33 for details
IMPORTANT: setting and checking the Date and Time is important for all logging
functions (trip or measurements). If there is a malfunction with the date and time
reset and if necessary replace the Ekip Touch battery (see 1SDH001000R0509)
Description
It allows activating an additional information page, accessible
by pressing the iTEST button twice from any page with the
diagnosis bar.
The configuration of the information on the new page is
allowed via Ekip Connect (page 118)
Rev. B
Default
English
00001
Default
Off
SACE Tmax XT2 – XT4 | 115