Electrical Installation
5.3 Wiring Schematic
230 V AC
50/60 Hz
3-phase
power
input
Load share
(optional)
+10 V DC
-10 V DC to +10 V DC
0/4-20 mA
-10 V DC to +10 V DC
0/4-20 mA
Illustration 5.2 Basic Wiring Schematic
1) Terminal 37 (optional) is used for Safe Torque Off. Refer to the VLT
instructions.
MG38A202
Operating Guide
TB5
R1
Space heater (optional)
91 (L1)
92 (L2)
93 (L3)
95
PE
Switch mode
88 (-)
power supply
89 (+)
10 V DC
15 mA
50 (+10 V OUT)
+
-
A53 U-I (S201)
53 (A IN)
ON=0/4-20 mA
A54 U-I (S202)
OFF=0 to ±10 V
54 (A IN)
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
P 5-00
24 V (NPN)
18 (D IN)
0 V (PNP)
24 V (NPN)
19 (D IN)
0 V (PNP)
20 (COM D IN)
24 V (NPN)
27
(D IN/OUT)
0 V (PNP)
24V
0V
24 V (NPN)
29
(D IN/OUT)
0 V (PNP)
24V
0V
24 V (NPN)
32 (D IN)
0 V (PNP)
24 V (NPN)
33 (D IN)
0 V (PNP)
37 (D IN)
1)
Danfoss A/S © 04/2018 All rights reserved.
(U) 96
(V) 97
(W) 98
(PE) 99
Regen +
(R+) 82
24 V DC
200 mA
(R-) 81
+
-
Regen -
Relay1
Relay2
(COM A OUT) 39
(A OUT) 42
S801/Bus Term.
OFF-ON
ON=Terminated
OFF=Open
5V
S801
RS485
(P RS485) 68
interface
(N RS485) 69
(COM RS485) 61
®
FC Series - Safe Torque Off Operating Guide for installation
Motor
Brake
resistor
(optional)
Regen (optional)
83
03
240 V AC, 2A
02
400 V AC, 2A
01
06
240 V AC, 2A
05
400 V AC, 2A
04
Analog output
0/4-20 mA
1
Brake temperature
(NC)
2
0V
RS485
(PNP) = Source
(NPN) = Sink
5
5