3 Operation
3.3
Addressing the motor via an analog interface of the
LOGO!
Table 3-2
No.
5.
The setting value (0 to 10V) for the motor
n
speed
setpoint
by the LOGO! expansion module AM2 AQ to
SINAMICS V20 and scaled into a frequency
setpoint (0 to 50Hz) there.
The lower and upper limit of the frequency
setpoint depend on the minimum and
maximum motor speed which has been
configured in SINAMICS V20 (P1080=min and
P1082=max).
6.
The motor connected to SINAMICS V20
accelerates or decelerates the frequency
n
setpoint (
setpoint
the frequency converter.
The duration of the acceleration and
deceleration phases depend on the ramp-up
time and ramp-down time (P1122=ramp-up
time and P1121=ramp-down time) configured
in SINAMICS V20.
Set23_RegSim
Entry ID: 23753479,
V2.3.S,
Function
is continuously transmitted
n
) supplied by
actual
02/2014
Comments
6.67V
= 33.35Hz
Control value
0
6.67V
5
V
0
25
Hz
33.35 Hz
Hz
50
33.35
25
∆n in t=
13.00
n
n
setpoint
actual
Example for P1082 = 50Hz and P1122 =10s
– 13.00
(33.35
)
Hz
Hz
*
50
Hz
10
50
– n
(n
)
set
act
*
P1121
P1082
4.07s
10s
11