Door Close (Command Given Via Digital Inputs) - Siemens SIDOOR ATD401W System Manual

Atd4xxw series, door control systems for industrial applications
Hide thumbs Also See for SIDOOR ATD401W:
Table of Contents

Advertisement

3.1.5

DOOR CLOSE (command given via digital inputs)

Description of function
The CLOSE DOOR command must remain present continuously in order to close the door.
After the door has closed, it is held in this position by the torque that can be adjusted by the
parameter "Continuous torque CLOSE" as long as the command remains present.
Note
If the commands CLOSE DOOR and OPEN DOOR are present simultaneously, the door
always moves in the OPEN direction.
SIDOOR ATD410W/ATD420W/ATD430W
See also section Free function blocks (FBLOCK) (Page 76).
Note
As an alternative, the signal can also be evaluated via the PLC (process image).
Connection
SIDOOR ATD401W:
The "CLOSE DOOR" function is connected to "Input 3" (X6). See also section Digital input
signals (Page 108).
For the door commands to be given via the digital inputs, "Main menu → General setup →
Special parameters → FBLOCK configuration → Standard input" must be selected in the
operating menu.
Signals
Signal
1 (voltage applied)
0 (voltage not applied)
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
Meaning
The CLOSE DOOR command is pending
The CLOSE DOOR command is not pending
SIDOOR functions
3.1 Basic functions
43

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sidoor atd420wSidoor atd410wSidoor atd430w

Table of Contents