Siemens SIDOOR ATD401W System Manual page 143

Atd4xxw series, door control systems for industrial applications
Hide thumbs Also See for SIDOOR ATD401W:
Table of Contents

Advertisement

Relay control
Table 4- 20
Relay control for PROFINET module
Terminal
Assignment
X100.1
CLOSE
X100.2
(closed)
X100.3
OPEN
X100.4
(open)
Connection
The wired relay connector is connected to connection X100.
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
Description
The relay is additionally influenced by the sensor configuration (parameter p4600).
For more, see also section Sensors and external sensor interface module
(ATD4xxW) (Page 152).
Sensor function test inactive
The system's internal door state "closed" is signaled via this relay (relay con-
tact is closed). This state is not only position-dependent. Note the following
conditions:
The "closed" state can only be achieved with a drive order.
The "closed" state cannot be achieved by external pushing.
The "closed" state can be terminated by means of a drive order or external
pushing.
Sensor function test active
The "TestOUT" sensor function test signal is output.
The system's internal door state "open" is signaled via this relay (relay contact is
closed).
This state essentially depends on the current door position.
The "open" state can be achieved both by means of a drive order and also by
external pushing.
The "open" state can be terminated by means of a drive order or external
pushing.
Controllers
4.5 Relay and fieldbus interfaces
143