Siemens SIDOOR ATD401W System Manual page 130

Atd4xxw series, door control systems for industrial applications
Hide thumbs Also See for SIDOOR ATD401W:
Table of Contents

Advertisement

Controllers
4.5 Relay and fieldbus interfaces
SIDOOR-specific parameters
The SIDOOR internal communication channel (internal bus) can be configured with the
following parameters:
● Data communication
● Baud rate
● Slave address
● Telegram type
● Cycle time
In order to establish error-free, stable communication, the settings on the connected
SIDOOR controller (internal bus) have to be matched.
Table 4- 11
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 User parameter byte 1
0
Table 4- 12
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 User parameter byte 1
0
130
User parameter byte 1
x
x
0
0
User parameter byte 2
x
x
0
0
x
Data communication
Data communication is deactivated if this bit is set
to 0.
Factory setting = 1 (activated)
x
x
Baud rate
The baud rate is set with bits 1 to 4.
Codes:
9600 = 0000
19200 = 0001
38400 = 0010
57600 = 0011
115200 = 0100
187500 = 0101
250000 = 0110
300000 = 0111
375000 = 1000
500000 = 1001
750000 = 1010
Factory setting = 115200 (0100)
Reserved
x
x
x
Slave address
The slave address is set with bits 0 to 4.
Address range = 0 to 31
Factory setting = address 1
Reserved
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sidoor atd420wSidoor atd410wSidoor atd430w

Table of Contents