Order number
Product
Power supply, type
Safety
Primary/secondary isolation
Galvanic isolation
Protection class
Leakage current
maximum
•
typical
•
CE mark
UL/cUL (CSA) approval
Explosion protection
FM approval
CB approval
Marine approval
Degree of protection (EN 60529)
EMC
Emitted interference
Supply harmonics limitation
Noise immunity
Operating data
Ambient temperature
during operation
•
–
Note
during transport
•
during storage
•
Humidity class according to EN 60721
Mechanics
Connection technology
Connections
Supply input
•
Output
•
Auxiliary
•
Width of the enclosure
Height of the enclosure
Depth of the enclosure
Required spacing
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
6EP3446-8SB10-0AY0
SITOP PSU8200
36 V/13 A
Yes
Safety extra low output voltage Vout according to
EN 60950-1
Class I
3.5 mA
0.9 mA
Yes
cULus-Listed (UL 508, CSA C22.2 No. 107.1),
File E197259
No
-
Yes
GL, ABS
IP20
EN 55022 Class B
EN 61000-3-2
EN 61000-6-2
-25 ... +70 °C
with natural convection
-40 ... +85 °C
-40 ... +85 °C
Climate class 3K3, no condensation
screw-type terminals
L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4
mm² single-core/finely stranded
+, -: 2 screw terminals each for 0.2 ... 4 mm²
13, 14 (alarm signal): 1 screw terminal each for
0.14 ... 1.5 mm²; 15, 16 (Remote): 1 screw termi-
nal each for 0.14 ... 1.5 mm²
70 mm
125 mm
125 mm
6.3 SITOP PSU8200 13A/36V 3-phase
Power supply
235