C.4 MEMOBUS/Modbus Setup Parameters
C.4 MEMOBUS/Modbus Setup Parameters
u MEMOBUS/Modbus Serial Communication
This section describes parameters necessary to set up MEMOBUS/Modbus communications.
H5-01: Drive Node Address
n
Sets the drive node address used for MEMOBUS/Modbus communications.
Note: After changing this parameter, the control power must be cycled to enable the new setting.
No.
H5-01
<1> If the address is set to 0, no response will be provided during communications.
For serial communications to work, each individual slave drive must be assigned a unique slave address. Setting H5-01
to any value besides 0 assigns the drive its address in the network. Slave address don't need to be assigned in sequential
order, but each address needs to be unique so that no two drives have the same address.
H5-02: Communication Speed Selection
n
Sets the MEMOBUS/Modbus communications speed.
Note: After changing this parameter, the control power must be cycled to enable the new setting.
No.
H5-02
H5-02
0
1
2
3
4
H5-03: Communication Parity Selection
n
Sets the parity used for MEMOBUS/Modbus communications.
Note: After changing this parameter, the control power must be cycled to enable the new setting.
No.
H5-03
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
H5-04: Stopping Method after Communication Error (CE)
n
Selects the stopping method after a communications error (CE) has occurred.
No.
H5-04
Setting 0: Ramp to stop (uses the deceleration time currently enabled)
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
228
Name
Drive Node Address
Name
Communication Speed Selection
Communication Speed
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
Name
Communication Parity Selection
Name
Stopping Method after Communication Error (CE)
Setting Range
0 to FF
Setting Range
0 to 5
H5-02
5
6
7
8
Setting Range
0 to 2
Setting Range
0 to 3
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Default
1F
<1>
Default
3
Communication Speed
38400 bps
57600 bps
76800 bps
115200 bps
Default
0
Default
3