Chapter 16 – Firmware Revision History
05/03/15 WJP
Added customer logic FCM real time parameter to access the 4-20mA output monitor value.
This is required for customer logic to see the 4-20mA signal being sent to an Analog
Control Valve since this is computed internally by the FCM.
05/04/15 TF
Fix: Fallback flow rate based on current flow rate. If unable to reach the desired flow
rate the Multiload will decrease the target flow rate. Previously the MultiLoad would use
the "Fallback Flow Rate" if it was configured no matter what the current state was (Low
Flow, High Flow, etc.). Now the MultiLoad will use the "Fallback Flow Rate" only during
High Flow and if configured, otherwise it will calculate a new flow rate based on the
deadbands.
05/05/15 MTS
Fix: Allow all of the network params to be read and set via terminal.
05/19/2015 WJP
Increased Firmware version to x.31.23
05/25/2015 MTS
Recycling some previously used configuration registers for some new IP configuration
parameters created a side effect that after a firmware upgrade, if the old register data is
loaded into the new IP parameters, an invalid IP address would be configured (0.0.0.8 or
0.0.0.16).
At startup these IP registers are now checked and if an invalid IP address is found to be
configured, an error message will be displayed and logged.
05/29/2015 WJP
Added ability to change the word order for 32 bit modbus registers.
Added new network configuration parameter "Modbus 32 Bit Little Endian" enable.
06/01/2015 TF
Fix: Logging of rejected parameters. In some cases MultiMate would save SCS specific
parameters which caused an excessive amount of rejections while loading a configuration.
This raised some concerns about what parameters were being rejected because the names were
being logged as "Unused" instead of the actual parameter names. The names of these
parameters will now be logged so there is no confusion about which parameters have been
rejected.
Fix: Printing of corrected density on a BOL. Previously the MultiLoad would print the
measured density instead of the corrected density.
Fix: Wrong Additive target was being saved to the transaction record. Over injection
volume was not included in the transaction record.
Enhancement: The W&M change log is now stored on to the SD Card. A new directory has been
created called "WEIGHTS_MEASURES_LOGS".
06/05/2015 TF
Added SD Card configuration menu to the SD Card screen.
Added new SD Card configuration parameters that gives the user the ability to configure
how long files are stored on the SD Card.
- Store Event Log Files in Days
- Store Audit Logs Files Days
- Store W&M Log Files in Days
- Store Report Files in Days
- Store Transaction Files in Days
Firmware Version 3/4.31.37
502
Need help?
Do you have a question about the MultiLoad II and is the answer not in the manual?
Questions and answers
Greetings, how can multiload ll totalizers be reset?
The resettable totalizers on the Toptech Systems MultiLoad II can be reset using the CLR (Clear) key. Non-resettable totalizers cannot be reset.
This answer is automatically generated