Chapter 6 – Additive Control
5. The Select Additives screen displays.
6. Select the additives that will be tested in the current session.
If multiple additives are assigned to the same test button, make sure that only one is enabled;
!
otherwise the others may inject when the button is pressed.
7. Press EXIT when all of the desired additives have been selected. This will return you to the Remote Additive
Calibration menu.
8. Select 'Collect Samples'.
9. The technician is prompted to remove the program key in order to lock the MultiLoad II keypad; this is
optional. Upon entering this screen, all of the additives that were enabled in the last step are now ready for
calibration. The appropriate additive pump contacts will be activated and will remain that way until the screen
is exited.